free quality report for PLCopenXML exports

Rules / timer-off-delay-in-own-branch

TOF is only called while its input is high: the off-delay never runs

An off-delay must count while its input is low. If it is only called inside a branch that requires that same input, there is no call when the command drops, and the elapsed time stays at zero.

Severity: Critical Rule id: timer-off-delay-in-own-branch Off-delay is not called when it should be counting

What the rule checks

An off-delay counts while its input is DOWN: drop the command, the delay runs, the output goes off after the setpoint. If the timer is only called inside a branch whose condition requires that same input, then at the moment the command is dropped the branch does not execute, there is no call, and the accumulated time stays at zero. The delay never ends and the equipment never stops. For an on-delay the same code is correct, since it is meant to count while the condition holds, so the rule looks only at TOF and TONOF. Found by enumerating combinations and confirmed with a scan emulator: the accumulated time stayed at zero under every input behaviour tried.

What it does to the plant

Depending on the surrounding code the output either drops at once with no delay or never drops: run-on and purge do not work as designed.

Example

Bad: the rule fires
FUNCTION_BLOCK FB_FanRunOnVAR_INPUT    xCmd : BOOL;END_VARVAR_OUTPUT    xFan : BOOL;END_VARVAR    tofRunOn : TOF;END_VARIF xCmd THEN    tofRunOn(IN := xCmd, PT := T#30S);    xFan := tofRunOn.Q;ELSE    xFan := FALSE;END_IF
Fixed: the rule is silent
FUNCTION_BLOCK FB_FanRunOnVAR_INPUT    xCmd : BOOL;END_VARVAR_OUTPUT    xFan : BOOL;END_VARVAR    tofRunOn : TOF;END_VARtofRunOn(IN := xCmd, PT := T#30S);xFan := tofRunOn.Q;

Both listings are run through the linter by an automated test: the rule fires on the first and stays silent on the second.

How to fix

  1. Call the timer unconditionally and pass the condition to its input: put t(IN := v, PT := …); outside the branch and keep the branch for the actions.
  2. Test the stop, not the start: starting works correctly in this code, and the defect only shows at shutdown.
Check your project

Upload a PLCopen XML or CODESYS .export file: the report is free and the code is not stored.

Local version on GitHub →

The same linter without uploading a file: command line and GitHub Action.

Related rules

2026-11-26

Processing happens in memory, and the uploaded code is not stored. The tool advises; code changes are up to the engineer (see what the linter can't see). What happens to your code → · Rule reference · Your code & privacy · Industry benchmark · Feedback · GitHub