DHW: the heating valve opens when the sensor fails

In the sensor-fault or not-AUTO branch the program must drive the valve to a safe position. For space heating "open" is usually right, for domestic hot water it is not: an open valve means full heat with no control. The rule belongs to the heating profile.

Severity: Warning Rule id: heating-dhw-fault-opens DHW: valve opens on a sensor fault

This rule belongs to the optional "heating" profile and only runs when the profile is enabled.

What the rule checks

In the sensor-fault branch (or "not AUTO") the program should drive the actuator to a safe position, and which position is safe depends on the circuit. For space heating, fully open is usually right: the building does not freeze. For domestic hot water, an open heating-side valve means maximum heat into the exchanger with no control: overheated water at the tap and a scalding risk. The rule only looks at DHW circuits, and only by explicit markers: DHW/GVS in the POU or output name. In the branch that runs on a sensor fault (IF NOT alarm … ELSE or IF alarm THEN) it looks for an "open" output set to TRUE. Without explicit circuit markers it stays silent. Which position is safe is the process engineer's call: the finding is a question, not a verdict.

What it does to the plant

Overheated water at the tap and a scalding risk when the DHW temperature sensor breaks.

Example

Bad: the rule fires
VAR_GLOBAL    xFaultDhw, xAutoDhw : BOOL;    rDhwTemp, rDhwSet : REAL;    dhw_valve_open, dhw_valve_close : BOOL;END_VARPROGRAM DhwValveIF NOT gvl.xFaultDhw AND gvl.xAutoDhw THEN    gvl.dhw_valve_open := gvl.rDhwTemp < gvl.rDhwSet - 2.0;    gvl.dhw_valve_close := gvl.rDhwTemp > gvl.rDhwSet + 2.0;ELSE    gvl.dhw_valve_open := TRUE;    gvl.dhw_valve_close := FALSE;END_IF
Fixed: the rule is silent
VAR_GLOBAL    xFaultDhw, xAutoDhw : BOOL;    rDhwTemp, rDhwSet : REAL;    dhw_valve_open, dhw_valve_close : BOOL;END_VARPROGRAM DhwValveIF NOT gvl.xFaultDhw AND gvl.xAutoDhw THEN    gvl.dhw_valve_open := gvl.rDhwTemp < gvl.rDhwSet - 2.0;    gvl.dhw_valve_close := gvl.rDhwTemp > gvl.rDhwSet + 2.0;ELSE    gvl.dhw_valve_open := FALSE;    gvl.dhw_valve_close := TRUE;END_IF

Both listings are run through the linter by an automated test: the rule fires on the first and stays silent on the second.

How to fix

  1. Agree the safe position of the DHW valve on a sensor fault with the process engineer; it is usually closed or a fixed position, not open.
  2. If opening is deliberate (for instance, there is independent overheat protection), say so in a comment inside the fault branch.
Check your project

Upload a PLCopen XML or CODESYS .export file: the report is free and the code is not stored.